Boiler Calculations for MCPD

Determination of the thermal input rating of a steam or hot water boiler

Download

As a rule of thumb, the chart below may be used to check the rated thermal input of a boiler – the default position where very accurate calculations are needed will be to ask the boiler manufacturer:

This table will be sufficient for almost all boiler plant in the range 1 – 50MW as most boiler ratings will fall between the MCPD ‘break points’ of 1, 5, 20 and 50MW.

Approximate steam boiler output for the nett heat input based on
kg/h F&A 100oC @ 85% efficiency

Nett boiler output

kg/h steam lb/h steam

1MW

1,350

3,000

5MW 6,780

15,000

20MW 27,125

60,000

50MW 67,800

150,000

 

Approximate hot water boiler output for the nett heat input based on
85% nett efficiency

Nett boiler output

MW hot water

1MW

0.85        (850kW)
5MW

4.25     (4,250kW)

20MW

17      (17,000kW)

50MW

42.5    (42,500kW)

Where it becomes necessary to calculate boiler thermal input ratings more accurately, the following notes may be helpful.

Steam Boilers are rated “from and at 100 ºC” (abbreviated to F&A100 ºC).  This is a measure of energy, not steam output.  For example, a boiler rated at 5000kg/hr F&A100 ºC can produce enough energy to change the state of 5000kg of water already at 100ºC to 5000kg of steam in one hour.   However, boilers usually take water at a lower temperature, typically 85 ºC, therefore requiring more energy input to reach the rated output.  The rating method describes the capability of the boiler assuming the water in it was already boiling.

Consequently the boiler rated at 5000kg/hr F&A 100 ºC in operation at 10 barg will actually produce around 4600 kg/hr.  This is important when calculating the size of boiler required to supply the demand of any process plant.   Some manufacturers will give a boiler rating in kW.  This is not an evaporation rate, and is subject to the same ‘from and at’ factor.

Boilers originally supplied with economisers that have now been removed, thereby slightly increasing the fuel input to replace the heat that was recovered from the economiser, will   need special consideration.

The efficiency part of the calculation is reasonably consistent since most plant will operate around 85% efficiency, although the final figure may depend on a number of details such as inherent losses and different construction types.  If in doubt, consult the boiler manufacturer for more details.

Nett v Gross

Calorific Value (CV) is the amount of heat energy produced (gross or nett) per volume of fuel and is measured in MJ/m3.  The Imperial equivalent is British Thermal Units per cubic foot (Btu/ft3).

The energy content can be expressed as an upper (or gross) value and a lower (or nett) value.  The difference between the two values is due to the release of energy from the condensation of water in the products of combustion.

Gross CV is the theoretical total available amount of heat energy in the fuel.

Nett CV is the practical amount of heat energy available from the fuel.

When gases burn, the exothermic reaction gives off heat.  Fuels with a high CV (such as LPG) give off much more heat per unit than those with a lower CV (Natural gas, less than half the CV of LPG).

As an example, the approximate difference between Gross CV and Nett CV for Natural Gas, which is predominantly (90%) methane, is 10%.  The nett calorific value of natural gas is the gross calorific value x 0.9.

Further reading

BOAS Assessors – the key to our success
13th February, 2024
 Inadvertent steam release results in tragic outcome on cruise ship
15th February, 2024
CEA Members help out at Museum
15th February, 2024
Emission Limit Values for Hydrogen and Non-Conventional Fuels
15th February, 2024

How to get in touch

Please do not hesitate to contact our friendly office team.

Become a membercontact us